Clearances
In most case, work units can be brought right up to the sides of the AGA, without the risk of damage from heat. Work tops should however stop short of the AGA top plate and not actually touch it. Any slight gap can be filled with a silicone sealant.
If the surrounding walls are to be tiled, then this must be done before the AGA is installed, as the tiles must be taken down below the AGA top plate level, not finish above it.
The rear wall must be non combustible for at least 25mm In a timber framed building, protection can be provided as shown below.

In a recess situation, If the adjacent right-hand wall protrudes forward beyond the front of the AGA, then an additional width clearance is required of 116mm on the right hand side, to allow the oven door to be opened sufficiently, as shown below

If the AGA is to be installed in a brick recess, then the minimum clearances should be increased by at least 10mm on either side, to allow for the walls being out of square and also for the natural dimensional variations found in castings.
At least 60mm clearance should be allowed above the insulating covers in their vertical, open position. |